PDD-8ACI TECHNICAL SALES BULLETIN

 

HOME

ABOUT ESD

PRODUCTS APP NOTES DOWN LOADS CONTACT ESD LIST PRICE

PDD-8ACI Power Distribution for Access Control with Fire Interface module

Controls and Distributes Power with 8 Control Relays with an EOL Fire trigger Interface

Power Interface for Access Control, CCTV, Fire, HVAC, Elevator, and general low voltage system control



Features:

Ø    8 Heavy duty Relays with individual Inputs and Status LED’s

Ø    Each Relay Input can be Activated from Low Current Open Collector, Normally Closed or Normally Open Switch

Ø    EOL End of Line Resistor  Fire Interface Master Trigger de-energizes all Output Relays that are Enabled to Unlock Doors or Shut Down Air Systems

Ø    Universal 12 – 24vdc power input

Ø    Available with Fuses or PTC Circuit Breakers

Ø    Each Output may be Individually Configured for:

·         Fire Trigger (FT) Enabled or (FTD) Disabled

·         FUSE model can provide optional Dry Contacts

·         N/O or N/C Option Configures the Relay Switched Output

Ø    Each Output 1-8 has a protected, continuous Output and a relay controlled Output

Ø    Outputs on PTC models are Class II power limited

Ø    Output Power can be AC or DC up to 32v

Ø    TRG LED Green Indicates Trigger Status

Ø    Control Power and Main Lock Power may be Isolated
(Separate Power Supplies) at Users Option

Ø    All Terminal Blocks are Pluggable by Channel & Function

Ø    Lifetime Warranty

 

  
 

pdd8aci

pd8acifig




DESCRIPTION / INSTRUCTIONS
 

The PDD-8ACI is a very versatile, compact way to distribute and control power for Access Control, Security, CCTV, Air Handling, and Elevator Control Systems with Fire Alarm Interface.  The PDD-8ACI is an 8 position power distribution board with individual input (IN) control for each output (OUT).  An EOL resistor trigger input (TRIG), will force all output relays to de-energize that are selected (FT).  In a typical insulation, the TRIG would be connected to a Fire Alarm panel via a set of contacts.  When the Fire Alarm trips, all enabled relays would be forced to be de-energized to unlock electric doors, shut down air systems, and return elevators to ground floor.  Any one of the 8 outputs could be utilized to provide a set of (TRIGGERED) form “C” status contacts to daisy chain other PDD-8ACI boards, latch, or provide feedback to a control system.  If the feedback contacts had to be dry, you would have to use a FUSE model or use a relay module like a RT-1.

Input/Output Terminals, Jumpers and LED
Details and Specifications

Control Power (- CONTR +) 2 position un-pluggable terminal block is used to power the coils of the relays.  The control voltage must be between 10 and 28 volts DC.  Each relay energized will draw 20ma of current.  By default, Control Power and Main Power are connected together with jumpers J1 & J2.  To utilize separate power for the control, J1 & J2 must be cut and suitable power connected to these terminals.

Main Power (- POWER +) 2 position un-pluggable terminal block provides the power to the outputs to be distributed.  This power input is limited to CONTR.  If J1 & J2 are cut and using separate supply for Main Power, then this power could be up to 32 volts AC or DC.  On fuse model the limit could be as high as 240v ac or dc observing safety and local electrical codes.  Current consumption would be total of each output circuit.


 

J1 & J2 are jumpers that connect to the Control Power, (-contr+) and the main lock power, (-power+) together for easy use of 1 power supply.  If you would like to use separate power supplies to fully isolate the control power to the output lock power, then cut Jumpers J1 & J2 located just above Control Power input.  If reconnecting J1 & J2 ever becomes necessary, then connect + to + and – to – at the main power and control power input terminal blocks.

Inputs (1-8 IN C) Eight, 2 position un-pluggable terminal blocks.  When IN & C are shorted together, the like number output relay will energize.  Each relay can also be energized by an open collector that is common to the control power, sinking 20ma for each input. Each of the C’s are areconnected to control negative power.

Input LED’s (1-8) Whenever an input is active (relay energized) the associated input red LED will illuminate.

Dry/Wet Option (1-8 Fuse Models)   Through a Fuse, the (+ Power) is connected to the swing arm of each Relay to distribute power to it’s output.  Removing the Fuse, removes the power from the relay.  The (+) now becomes the Common Swing Arm and the “O” is the N/O or N/C contact as selected with jumper.

Outputs (1-8 OUT C, +, O) Eight, 3 position un-pluggable terminal blocks.  “C” is Power Common and is connected to (- power).  (+) is the relay swing arm.  SO is the relay switch output as selected with N/O or N/C selector jumper.

Output Relay Contacts Selector (1-8 NC/NO) This selector located just above each output selects whether the N/C or N/O contacts are connected to the (O) switch output terminal. With N/C selected, output would be normally ON, or connected to swing arm.  With N/O selected, output would turn ON, or close when input is activated.

Fire Alarm Interface Trigger (2.2K EOL TRIG)  2 position un-pluggable terminal block.  This input must see the 2.2K ohm end of line resistor to be in the normal


 

 condition.  A change in resistance of + or – 60% caused

 by shorting or opening the EOL will cause the trigger activate, lighting the Trig LED, and de-energize all the enabled relays.  The EOL should be placed at the end of the line to supervise the wire run from module to Fire alarm panel. 

TRIG LED (TRIG) Green LED normally ON.  Whenever the Trigger is active the LED will be OFF.

Trigger Feedback

The PDD-8ACI module does not have a dedicated relay contacts to provide feedback; however any of the 8 outputs can be utilized to provide a trigger status feedback.  This feedback can be used to make the trigger latch, provided feedback to control panel, or daisy chain to trigger other PDD-8ACI’s.

Ordering Information

PDD-8ACIACI” module only with 2 Amp Fuses

PDD-8ACIC “ACIC” module only with 1.23 Amp PTC’s

SPS-5ELC81ACI  SPS-5 power supply in a large enclosure with a PDM-8C distribution board and 1 PDD-8ACI fused module

Each ACI takes the space of a standard PDM-8.  We do not charge extra for mounting when purchased with a cabinatecabinet power supply.


 
SPECIFICATIONS
 

Control (-contr+) .  11 - 28vdc @ 160ma (20ma per relay)

Main Power (-power+) ..........................  0–32v ac or dc

Note: Must cut J1 & J2 when using AC on Main Power

Power Current ........................................  Total Output

Input relay activate current (spike protected)........ 20ma

Terminal blocks un-plugable ..  5mm spacing 14–28 awg

PTC Outputs 1-8 Power Limited Class II ..................  1.23 Amp

Fused Outputs 1-8 Non Power Limited .............   2 Amp

Output Relays 1-8 Contacts rating ...........   7A 125VAC

Trigger Input  ..............................................  2.2K EOL

Operating Temperature ...........................   -40o ~ +85C

Mounting Holes (4)  3.4” x 4.5” Weight:  ...............   8oz  

 

 


 
pdf PDD-8ACI Technical Sales / Instructions


Electronic Security Devices Incorporated 09/20/05 jdb
Specifications are subject to change without notice

 